Understanding BS 8558: The Essential Guide to Designing and Maintaining Water Systems
- Identify fluid categories – Dishwasher (Cat 5 due to detergents + heat + organics) requires an air gap (Type AUK2).
- Select backflow prevention – A reduced pressure zone (RPZ) valve with local atmospheric vent.
- Check TMV requirements – Hot water to taps must be ≤ 44 °C at outlet; specify TMV3.
- Verify stagnation – Hot water return pipe diameter sized for ≥ 0.5 m/s flow at all TMVs.
- Calculate demand – Not simply adding 15 mm pipes; use simultaneous usage factors from BS 8558 Annex C.
Stagnation Prevention: Advises on avoiding "dead legs"—lengths of pipe where water might sit still—to minimize the risk of bacterial growth. 2. Installation and Commissioning bs 8558 pdf
Part 2: The control of legionella bacteria in hot and cold water systems Understanding BS 8558: The Essential Guide to Designing